Motor Full-Load Current Table (NEC 430.250)
Full-load amps for three-phase motors from 0.5 to 200 HP at 200 to 575 V, with the sizing rules and a 400 V estimate.
Three-Phase Motor Full-Load Current Table (NEC 430.250)
This table lists the full-load current (FLC) of three-phase induction motors from NEC Table 430.250, in amperes, for the standard US voltages. The NEC requires these table values (not the nameplate) to size motor branch-circuit conductors and short-circuit protection, while the nameplate current is used for the overload relay.
| HP | kW (approx.) | 200 V (A) | 208 V (A) | 230 V (A) | 460 V (A) | 575 V (A) |
|---|---|---|---|---|---|---|
| 0.5 | 0.37 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 |
| 0.75 | 0.56 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 |
| 1 | 0.75 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 |
| 1.5 | 1.1 | 6.9 | 6.6 | 6 | 3 | 2.4 |
| 2 | 1.5 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 |
| 3 | 2.2 | 11 | 10.6 | 9.6 | 4.8 | 3.9 |
| 5 | 3.7 | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 |
| 7.5 | 5.6 | 25.3 | 24.2 | 22 | 11 | 9 |
| 10 | 7.5 | 32.2 | 30.8 | 28 | 14 | 11 |
| 15 | 11.2 | 48.3 | 46.2 | 42 | 21 | 17 |
| 20 | 14.9 | 62.1 | 59.4 | 54 | 27 | 22 |
| 25 | 18.6 | 78.2 | 74.8 | 68 | 34 | 27 |
| 30 | 22.4 | 92 | 88 | 80 | 40 | 32 |
| 40 | 29.8 | 120 | 114 | 104 | 52 | 41 |
| 50 | 37.3 | 150 | 143 | 130 | 65 | 52 |
| 60 | 44.8 | 177 | 169 | 154 | 77 | 62 |
| 75 | 56.0 | 221 | 211 | 192 | 96 | 77 |
| 100 | 74.6 | 285 | 273 | 248 | 124 | 99 |
| 125 | 93.2 | 359 | 343 | 312 | 156 | 125 |
| 150 | 111.9 | 414 | 396 | 360 | 180 | 144 |
| 200 | 149.2 | 552 | 528 | 480 | 240 | 192 |
Values are for typical 1,750 rpm (4-pole) induction motors running at normal speed with normal torque characteristics. Motors built for especially low speeds, high torque or multi-speed operation can draw more current, so use the nameplate for those. The kW column is HP × 0.746 for reference only.
How the table is used
Conductors: at least 125% of the table FLC (NEC 430.22). Short-circuit protection: an inverse-time breaker is limited to 250% of FLC, a dual-element time-delay fuse to 175% and a non-time-delay fuse to 300% (Table 430.52), with a rounding-up allowance if the motor will not start. Overload relay: about 125% of the nameplate current for motors with a service factor of 1.15 or more, and 115% for others (430.32).
2. Conductor ampacity: 14 × 1.25 = 17.5 A minimum.
3. Maximum inverse-time breaker: 14 × 2.5 = 35 A.
4. Overload relay: if the nameplate says 13 A and the service factor is 1.15, set it to about 13 × 1.25 = 16.3 A.
The motor branch-circuit calculator does the complete sizing, including wire and disconnect.
Using it for a 400 V, 50 Hz motor
NEC 430.250 covers 460 V, not 400 V. For motors outside North America, take the current from the nameplate, or estimate it from the power: I = kW × 1000 ÷ (√3 × 400 × PF × η). As a rough guide, a typical four-pole induction motor on 400 V draws about 1.8 to 2 A per kW of shaft power at full load. For example, a 7.5 kW motor with an efficiency of 0.88 and a power factor of 0.85 draws 7,500 ÷ (1.732 × 400 × 0.85 × 0.88) = 14.5 A. Real motors vary by manufacturer, so the nameplate always wins.
- Sizing the cable from the nameplate. The code table value is used for conductors and short-circuit protection; the nameplate is for the overload relay.
- Forgetting the starting current. Across-the-line starting draws about 5 to 8 times FLC for a short time. Breaker and wire sizing rules already allow for it, but the supply must be able to handle it.
- Using the 460 V column on a 400 V supply. The current is higher on a lower voltage for the same power.
- Ignoring voltage drop. A long run to a motor can drop enough voltage to cause hard starting. Check it with the voltage drop quick table.
Frequently asked questions
What is the full-load current of a 10 HP motor? From NEC Table 430.250, a three-phase 10 HP motor is 28 A at 230 V, 14 A at 460 V and 11 A at 575 V.
Do I use the nameplate or the table to size the wire? Use the table value for the conductors and short-circuit protection (NEC 430.6). Use the nameplate current for the overload protection.
How do I find motor current at 400 V? Use the nameplate. If you only have the power, use I = kW × 1000 ÷ (√3 × 400 × PF × efficiency), or about 1.8 to 2 A per kW as a rough guide.
Safety note. These figures are reference values and not a substitute for your local electrical code or a qualified electrician.