Voltage Drop Quick Table (Max Cable Length for 3% Drop)

Find the longest cable run that stays within 3% voltage drop for 12 V DC and 230 V AC, by wire size and current.

Voltage Drop • Copper • 20°C

Voltage Drop Quick Table: Maximum Cable Length for 3% Drop

Voltage drop is the voltage lost along a cable because of its resistance. Too much drop makes lights dim, motors run hot and electronics reset. A common design target is 3% for a branch circuit and 5% in total from source to load. These tables give the longest run (one way, in metres) that stays within 3%, so you can size a cable without a calculator.

DC or single-phase: Vdrop = 2 × L × I × R  •  Three-phase: Vdrop = √3 × L × I × R
L = one-way length (m), I = current (A), R = conductor resistance (Ω/m = Ω/km ÷ 1000)

Table 1: 12 V DC, maximum one-way length (m) for 3% drop (0.36 V)

Wire size5 A10 A15 A20 A30 A40 A50 A
16 AWG2.71.40.90.70.50.30.3
14 AWG4.32.21.41.10.70.50.4
12 AWG6.93.52.31.71.20.90.7
10 AWG115.53.72.71.81.41.1
8 AWG178.75.84.42.92.21.7
6 AWG28149.36.94.63.52.8
4 AWG442215117.45.54.4
2 AWG70352318128.87.0
1/0 AWG112563728191411
2/0 AWG141704735231814
4/0 AWG2241127556372822

Other voltages and limits: for 24 V multiply the length by 2, for 48 V by 4. For a 5% limit multiply by 1.67, for 2% by 0.67. Lengths are for copper at 20°C; a hot cable (about 70°C) has roughly 20% more resistance, so multiply by 0.8 for hot installations. Currents are in amps across the top row.

Table 2: 230 V single-phase AC, maximum one-way length (m) for 3% drop (6.9 V)

Copper size6 A10 A16 A20 A25 A32 A
1.5 mm²48291814118.9
2.5 mm²784729231915
4 mm²1257547373023
6 mm²18711270564535
10 mm²314189118947559
16 mm²50030018815012094
25 mm²791475297237190148
35 mm²1097658411329263206

Resistance values are IEC 60228 maximum DC resistance at 20°C. Reactance is ignored, which is acceptable for these small sizes; it becomes noticeable for larger cables on long AC runs. Use 400 V three-phase by replacing the factor 2 with √3 (1.73) and the allowed drop with 3% of 400 V.

Table 3: Voltage drop per amp per metre

Multiply by the current and the one-way length (m) to get the drop in millivolts.

Wire sizeR (Ω/km)DC / single-phase (mV/A/m)Three-phase (mV/A/m)
16 AWG13.1726.322.8
14 AWG8.2816.614.3
12 AWG5.2110.49.02
10 AWG3.286.555.68
8 AWG2.064.123.57
6 AWG1.302.592.24
4 AWG0.821.631.41
2 AWG0.511.030.888
1/0 AWG0.320.6450.558
2/0 AWG0.260.5110.443
4/0 AWG0.160.3220.278
Worked example: 20 A load, 6 m from a 12 V battery
Goal: keep the drop under 3% (0.36 V).
1. Try 8 AWG: R = 2.061 Ω/km, so Vdrop = 2 × 6 × 20 × 0.002061 = 0.49 V (4.1%). Too much.
2. Try 6 AWG: R = 1.296 Ω/km, so Vdrop = 2 × 6 × 20 × 0.001296 = 0.31 V (2.6%). Within 3%.
3. Table 1 agrees: 6 AWG at 20 A allows 6.9 m one way, 8 AWG only 4.4 m.
4. Also check the ampacity: 6 AWG at 20 A is well inside the wire gauge table limits.
Common mistakes
  • Using the total round-trip length as the length. These tables already include the return conductor; enter the one-way distance from source to load.
  • Checking only ampacity. Low-voltage DC systems (12 V, 24 V solar and battery wiring) usually fail on voltage drop long before they fail on current.
  • Ignoring starting current. Motors and compressors draw several times their running current for a moment, which can pull a long cable below the voltage the load needs.
  • Applying the 3% limit to every part. The recommended totals are about 3% for branch circuits and 5% for feeder plus branch together. Check your local code.

Frequently asked questions

How much voltage drop is acceptable? Many codes and design guides recommend no more than 3% on a branch circuit and 5% overall. Sensitive electronics and low-voltage DC systems often need less.

How do I reduce voltage drop? Use a thicker conductor, shorten the run, raise the system voltage (for example 24 V instead of 12 V), or reduce the current.

Why is the drop worse on 12 V than on 230 V? The same cable loses the same number of volts, but 0.36 V is 3% of 12 V while it is only 0.16% of 230 V.

Safety note. These figures are reference values and not a substitute for your local electrical code or a qualified electrician.