← Back to ElectroLab
Protection & Power QualityIEEE 519-2022 • IEC 61000-2-4 • EN 50160

Total Harmonic Distortion (THD)

Enter the fundamental and harmonic percentages to get THD or TDD, the dominant harmonic and an IEEE 519 limit check.

THD = √(ΣXh²) / X1 × 100  •  TDD = √(ΣIh²) / IL  •  RMS = X1√(1 + THD²)
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Harmonic magnitudes are percentages of the fundamental and h = 2 to 15 (even orders and h = 8, 10, 12, 14 are not listed; enter their root-sum-square into a nearby order if needed). Voltage limits are typed from memory (THD 8 / 5 / 2.5 / 1.5 %, individual 5 / 3 / 1.5 / 1.0 % by bus class): verify against IEEE 519-2022 before you rely on them. Current mode computes TDD = √(ΣIh²) / IL and compares it with the total limit for the Isc/IL ratio (5 / 8 / 12 / 15 / 20 %); the individual current limits, which differ by harmonic order and are lower for even harmonics, are not checked here. Real limits apply at the point of common coupling.

IEEE 519-2022 • IEC 61000-2-4 • EN 50160

Total Harmonic Distortion: Measuring What Non-Linear Loads Do to the Waveform

Core Engineering Principles

Any load that draws current in pulses instead of a smooth sine pushes harmonics back into the system: variable frequency drives with diode rectifiers, switch-mode supplies in servers, LED drivers, battery chargers and arc furnaces. Each harmonic is a sine at a whole-number multiple of the line frequency, and THD is their root-sum-square divided by the fundamental, not by the total RMS. Current distortion is the cause; voltage distortion is the symptom, produced as that current flows through the source impedance.

The damage is mostly heat and resonance. Harmonic currents raise eddy-current losses in transformers, so we derate them or buy K-rated units. Triplen harmonics (3rd, 9th, 15th) from single-phase loads add in the neutral instead of cancelling; we have seen undersized neutrals cook on office floors full of computers. A capacitor bank and the source inductance form a parallel resonance, and if it lands near the 5th or 7th, a modest harmonic current becomes a large voltage. We judge current as TDD, normalised to demand current, because a lightly loaded drive shows a terrible THD on a tiny current.

THD = √(Σ Xh² for h ≥ 2) / X1 × 100  •  TDD = √(Σ Ih²) / IL × 100
RMStotal = X1 × √(1 + THD²)  •  Distortion factor = 1 / √(1 + THD²)

NEC & Standard References

IEEE 519-2022 sets harmonic limits at the point of common coupling (PCC), the point where the utility and other customers connect: voltage limits by bus voltage class, and current limits by short-circuit-to-demand current ratio. IEC 61000-2-4 defines compatibility levels for industrial plants. EN 50160 describes public supply voltage characteristics, including harmonics. The limits in this calculator are typed from memory, so verify against IEEE 519-2022 and your adopted edition before signing a compliance report.
Worked Example: 277 V Bus with Mixed Drive and LED Load
Given: V1 = 277 V, bus class ≤ 1 kV (limits THD 8%, individual 5%). Harmonics in % of fundamental: h3 1.5, h5 3.5, h7 2.2, h11 1.1, h13 0.7.
1. Squares: 2.25 + 12.25 + 4.84 + 1.21 + 0.49 = 21.04.
2. THD = √21.04 = 4.587%, which is under the 8% limit.
3. Dominant harmonic is the 5th at 3.5%, or 277 × 0.035 = 9.70 V; it is under the 5% individual limit.
4. RMS total = 277 × √(1 + 0.04587²) = 277.29 V.
5. Distortion factor = 1 / 1.00105 = 0.9989.
6. Compliant, but the 5th is 70% of its limit.
Safety & Installation Rules
  • Light-load THDi misleads. A drive at 10% load can show 60% THD on a trivial current; judge it by TDD.
  • Measure at the right point. Limits apply at the PCC, not at the drive terminals.
  • Check for capacitor resonance. Use detuning reactors on harmonic-rich buses.
  • Watch the neutral. Triplen currents add there, so size it at 200% where single-phase electronics dominate.
  • Use a true-RMS meter. Average-responding meters read low on distorted current.