← Back to ElectroLab
Solar & EVIEEE 485 • IEC 60896 • Peukert

Battery Peukert Capacity Calculator

Enter rated capacity, rating period, Peukert exponent and load to see the real runtime and the capacity you actually get.

t = H × (C / (I × H))k  •  Aheff = I × t
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Peukert’s law t = H (C / I H)k is an empirical model. It has no temperature or age term and is best between about 0.05C and 1C. The chemistry k ranges are typical values, not ratings; the exponent you enter is used. Power mode converts I = P / V at the nominal bank voltage, so a real constant-power load draws more current as the voltage sags. Usable Ah = DoD × effective capacity. Confirm with the manufacturer discharge tables (IEEE 485 / IEC 60896).

IEC 60896 • IEEE 485 • IEEE 1188 • Peukert’s Law

Peukert’s Law: Why a Battery Gives Less Than Its Label at High Current

Core Engineering Principles

A lead-acid label says 100 Ah, and the small print says at the 20-hour rate. That means the cell was drained over 20 hours, about 5 A, to its end voltage. Pull 40 A and the plates cannot keep up: acid at the plate surface is used faster than diffusion replaces it, and you hit cut-off with charge still in the cell. Wilhelm Peukert described it in 1897 with an empirical power law, t = H × (C / (I × H))k. We read k as how hard the battery punishes high current. Flooded lead-acid sits around 1.2–1.4, AGM near 1.05–1.15, gel 1.1–1.25 and LiFePO4 only 1.01–1.05, so lithium behaves almost like an ideal tank.

Effective capacity, I × t, is what you really get at a given load. You can measure k yourself: discharge the battery at two currents, record both runtimes to the same end voltage, and apply k = (log t2 − log t1) / (log I1 − log I2). Do not trust the law blindly. It ignores temperature, so a cold battery loses more than predicted. It ignores age, since k creeps up as plates sulfate. It fails at very low currents, where self-discharge dominates, and at very high ones, where sag and heating take over. Treat it as an estimate between about 0.05C and 1C and check critical jobs against manufacturer tables.

t = H × (C / (I × H))k  •  Aheff = I × t
Imax = (C / H) × (H / ttarget)1/k
k = (log t2 − log t1) / (log I1 − log I2)

NEC & Standard References

IEC 60896-11 and IEC 60896-21/-22 define the general requirements and test methods for stationary lead-acid batteries,. IEEE 485 is the recommended practice for sizing stationary lead-acid batteries, using manufacturer discharge data. IEEE 1188 covers maintenance, testing and replacement of VRLA batteries including capacity tests. Verify the editions that apply.
Worked Example: 100 Ah Flooded Bank Feeding a 40 A Load
Given: C = 100 Ah at H = 20 h, k = 1.25, I = 40 A, DoD limit 50%, target runtime 5 h.
1. C / (I × H) = 100 / 800 = 0.125, and 0.1251.25 = 0.0743.
2. t = 20 × 0.0743 = 1.487 h, which is 1 h 29 min.
3. Effective capacity = 40 × 1.486 = 59.5 Ah, or 59.5% of rated. The C-rate is 40 / 100 = 0.40C.
4. To a 50% limit: 0.5 × 59.46 = 29.7 Ah, giving 0.743 h, or 45 min.
5. An ideal battery (k = 1) would run 100 / 40 = 2.5 h.
6. For a 5 h target: I = (100 / 20) × (20 / 5)1/1.25 = 15.2 A.
Safety & Installation Rules
  • Check the rating period. Marketing Ah are often quoted at the 100 h rate; compare batteries at the same H.
  • Inverter draw rises as voltage falls. A constant-power load pulls more amps near the end, so enter a low average voltage.
  • Never compare Ah across chemistries. A 100 Ah lithium battery delivers far more at 40 A than a 100 Ah flooded battery.
  • Peukert has no temperature term. Derate separately for cold and age.
  • Above 1C, stop. Use the manufacturer’s tables.