Three-Phase Power Formulas & Current Tables

Formulas for kW, kVA and line current, with lookup tables for 400 V and 415 V systems and a worked example.

Three-Phase • kW • kVA • 400 V

Three-Phase Power Formulas and Current Tables

These formulas apply to a balanced three-phase load, such as a motor, a heater bank or a transformer, where the three line currents are equal. VL is the voltage between two phases (line-to-line). In Sri Lanka and many other 50 Hz countries the low-voltage supply is 400 V between phases and 230 V from phase to neutral, so VL = 400 V is used in the tables below.

kW = √3 × VL × IL × PF ÷ 1000  •  kVA = √3 × VL × IL ÷ 1000
√3 = 1.732

Formula table

QuantityFormula (balanced load)
Apparent power S (kVA)S = √3 × VL × IL ÷ 1000
Active power P (kW)P = √3 × VL × IL × PF ÷ 1000
Reactive power Q (kVAr)Q = √(S² − P²) = S × sin φ
Line current from kWIL = P × 1000 ÷ (√3 × VL × PF)
Line current from kVAIL = S × 1000 ÷ (√3 × VL)
Motor input currentIL = Pshaft × 1000 ÷ (√3 × VL × PF × η)
Power factorPF = P ÷ S = cos φ
Star (wye) connectionVL = √3 × Vphase; IL = Iphase
Delta connectionVL = Vphase; IL = √3 × Iphase

Table 1: Line current for a given kVA (balanced load)

Use it for transformers, generators and UPS ratings. Current at 400 V is 1.443 A per kVA, and at 415 V it is 1.391 A per kVA.

RatingCurrent at 400 V (A)Current at 415 V (A)
1 kVA1.41.4
5 kVA7.27.0
10 kVA14.413.9
15 kVA21.720.9
20 kVA28.927.8
25 kVA36.134.8
30 kVA43.341.7
40 kVA57.755.6
50 kVA72.269.6
63 kVA90.987.6
75 kVA108.3104.3
100 kVA144.3139.1
125 kVA180.4173.9
160 kVA230.9222.6
200 kVA288.7278.2
250 kVA360.8347.8
315 kVA454.7438.2
400 kVA577.4556.5
500 kVA721.7695.6
630 kVA909.3876.5
800 kVA1154.71113.0
1000 kVA1443.41391.2

Table 2: Line current at 400 V for a given kW and power factor

The kW here is the electrical input power of the load. For a motor given by its shaft output, also divide by efficiency (see the motor formula above).

LoadPF 1.0 (A)PF 0.9 (A)PF 0.85 (A)PF 0.8 (A)
1 kW1.41.61.71.8
2.2 kW3.23.53.74.0
3 kW4.34.85.15.4
4 kW5.86.46.87.2
5.5 kW7.98.89.39.9
7.5 kW10.812.012.713.5
11 kW15.917.618.719.8
15 kW21.724.125.527.1
18.5 kW26.729.731.433.4
22 kW31.835.337.439.7
30 kW43.348.150.954.1
37 kW53.459.362.866.8
45 kW65.072.276.481.2
55 kW79.488.293.499.2
75 kW108.3120.3127.4135.3
90 kW129.9144.3152.8162.4
Worked example: a 30 kW load at power factor 0.85 on 400 V
1. Line current: I = 30,000 ÷ (1.732 × 400 × 0.85) = 50.9 A.
2. Apparent power: S = 30 ÷ 0.85 = 35.3 kVA.
3. Reactive power: Q = √(35.3² − 30²) = 18.6 kVAr.
4. If the power factor is raised to 0.95, the current falls to 45.6 A, which is why a utility or a generator rating cares about PF. See the power factor correction calculator.
Common mistakes
  • Using phase voltage in the formula. With the √3 formula you must use the line-to-line voltage (400 V), not 230 V.
  • Confusing kW and kVA. Breakers, cables and generators carry the current set by kVA, while the energy bill follows kW.
  • Ignoring efficiency on motors. A 7.5 kW motor rating is shaft output, so its input current is higher than 7,500 ÷ (1.732 × 400).
  • Assuming the load is balanced. If the three phases carry different currents, calculate each phase separately or use the neutral current calculator.

Frequently asked questions

What is the three-phase power formula? P = √3 × VL × IL × power factor, with the line-to-line voltage VL and the line current IL.

How do I convert kW to amps on three-phase? Divide the power in watts by √3 × line voltage × power factor. For example, 10 kW at 400 V and PF 0.9 draws about 16 A.

What is the difference between star and delta? In star the line voltage is √3 times the phase voltage and line current equals phase current. In delta the line current is √3 times the phase current and line voltage equals phase voltage.

Safety note. These figures are reference values and not a substitute for your local electrical code or a qualified electrician.